flow_confirm_drill.py walks the driver's suspicion/confirmation state machine through every verdict with real pump-off transients in one M8 session; flow_escalate_drill.py exercises the starved-re-check escalation against a short GFCOOL_CONFIRM_MAX_S. BRINGUP records the triage resolution (the 2026-08-03 faults were a real transient stagnation, probable pump airlock - the check was right), the slug/ circulation measurements, and the new check semantics.
86 lines
2.2 KiB
Python
86 lines
2.2 KiB
Python
#!/usr/bin/env python3
|
|
"""Bench drill for the starved-re-check escalation path.
|
|
|
|
Runs ON THE BOARD against a controller started with a short
|
|
confirmation budget (GFCOOL_CONFIRM_MAX_S=45; see the runbook for the
|
|
manual start line). With the pump off, the job-start check reads
|
|
over-limit -> SUSPECT; the cooked stagnant loop then cannot pass the
|
|
settle gate within 45 s, so the budget expires and the driver must
|
|
escalate: "COOLANT FLOW FAULT: no clean re-check within 45 s".
|
|
|
|
Prints PASS/FAIL and leaves the machine idle: M9 sent, pump on,
|
|
heater off.
|
|
"""
|
|
import select
|
|
import socket
|
|
import time
|
|
|
|
T0 = time.monotonic()
|
|
|
|
|
|
def el():
|
|
return time.monotonic() - T0
|
|
|
|
|
|
def log(msg):
|
|
print('%7.1f %s' % (el(), msg), flush=True)
|
|
|
|
|
|
def pump(on):
|
|
with open('/sys/glowforge/thermal/water_pump_on', 'w') as f:
|
|
f.write('1' if on else '0')
|
|
log('** pump -> %s' % ('ON' if on else 'OFF'))
|
|
|
|
|
|
s = socket.create_connection(('127.0.0.1', 23), timeout=5)
|
|
s.setblocking(False)
|
|
buf = b''
|
|
|
|
|
|
def wait_msg(substrs, deadline):
|
|
global buf
|
|
while el() < deadline:
|
|
r, _, _ = select.select([s], [], [], 0.2)
|
|
if not r:
|
|
continue
|
|
data = s.recv(4096)
|
|
if data:
|
|
buf += data
|
|
while b'\n' in buf:
|
|
line, buf = buf.split(b'\n', 1)
|
|
line = line.strip().decode('ascii', 'replace')
|
|
if line.startswith('[MSG'):
|
|
log('<< ' + line)
|
|
for m in substrs:
|
|
if m in line:
|
|
return line
|
|
return None
|
|
|
|
|
|
ok = True
|
|
try:
|
|
time.sleep(0.5)
|
|
pump(False)
|
|
log('--- M8 with the pump off')
|
|
s.sendall(b'M8\n')
|
|
|
|
if wait_msg(['FLOW SUSPECT'], el() + 180) is None:
|
|
log('!! no SUSPECT within 180 s')
|
|
ok = False
|
|
elif wait_msg(['no clean re-check within'], el() + 120) is None:
|
|
log('!! no escalation FAULT within 120 s of the suspect')
|
|
ok = False
|
|
finally:
|
|
try:
|
|
s.sendall(b'M9\n')
|
|
time.sleep(1.0)
|
|
except OSError:
|
|
pass
|
|
s.close()
|
|
pump(True)
|
|
with open('/sys/glowforge/thermal/heater_pwm', 'w') as f:
|
|
f.write('0')
|
|
log('--- M9 sent, pump on, heater off')
|
|
|
|
print('ESCALATION DRILL %s' % ('COMPLETE' if ok else 'FAILED'), flush=True)
|