ScottW514 4e0c90b5a5 The pulse-header envelope settled; the SoC die watched; item 19 closed
forgectrl pin b27398a: the SoC die joins the watched board temperatures
(/status temps soc_c and the kernel's CPU cooling state soc_throttle,
the Status tab, the per-job range line naming a throttle), a throttle
starting or ending is logged, and the supply sensor stays a raw count by
decision (its heatsink cannot be reached with a thermometer while the
machine runs). forgefirm-app pin e65cfc2 (0.1.16+git): every pulse-header
key without an applier is declared with its reason or counted as
undecided in the job log, and CLOUD.md carries one disposition table for
the whole header.

BRINGUP: the pulse-header envelope item is closed. Its durable content is
in the facts bank ("The factory's envelope, decoded": the mandatory tags,
the empty tach windows, the factory's pause and fail tiers, the
per-sensor units, the unarmed flow controller, and ForgeFIRM's answer
with its catalog proofs) and in the "Deliberately not gated" paragraph,
which names every declared family. Item 19 is now the bench-measured
head crash and rail-contact detector; the fire-watch item holds the
header's lid IR thresholds as its prior. The facts bank also records the
SoC's own thermal guard (85 C passive, 90 C critical, no heatsink on the
factory board) and the board temperatures at idle.

Catalog: cooling.gate-off checks the die field, the unthrottled state at
idle and the widened run-end line (the unit fake mirrors it). COOLING
section 9 and the SERVICES verification status describe the present.
2026-08-22 14:24:50 -04:00

26 KiB
Raw Blame History

Cooling and airflow

The tube is water-cooled and the enclosure is air-cleared, and both matter while the laser fires: coolant that has stopped circulating will let a tube overheat within a cut, and smoke that is not pulled out spoils the work and fogs the optics. ForgeFIRM runs this as one service — the cooling engine — that owns every piece of thermal hardware and answers one question at a time for whichever controller is running: is it safe to fire right now?

This page explains what the system is made of, how it decides, what you will see when it intervenes, and what you can tune.


1. What the hardware is

The coolant loop is closed: a pump, a radiator with fans, the laser tube, and two thermistors — one upstream of the tube and one downstream of a small inline heater. Pro machines are specified with a thermoelectric cooler (TEC) on the loop; the board cannot tell whether one is fitted (§9). The heater exists for diagnostics, not for warming the machine up: it is how the engine proves the coolant is actually moving (§4).

The airflow path has four independently driven pieces:

Piece What it does
Exhaust blower pulls smoke out of the enclosure
Two intake fans feed clean air in behind it
Air assist (in the head) blows the cut line clear at the focal point
Purge air (in the head) keeps the optics clean; on whenever the machine is on

Every fan reports a tachometer, so the engine can tell a commanded duty from an actual airflow, and the panel shows real speeds rather than setpoints.

Coolant temperature is read, not guessed. Both thermistors are converted with the factory's own beta-equation curve, checked against a thermometer. A sensor reading at either rail is treated as open or shorted — not as a temperature.


2. One owner, two clients

The cooling engine lives in forgectrl, the machine-services daemon, and it is the only thing that writes fans, pump, TEC and heater. Whichever controller is running — GRBL or cloud — is a client of it, over two channels:

  • The controller reports its job state about once a second: idle, running or cooling down, whether the laser is armed, and (in cloud mode) the fan duties the job asks for. The reports are level-triggered, so a lost one simply corrects itself on the next.
  • The engine publishes a verdict the controller reads and enforces in its own process: may the laser fire, should the job hold, may it resume.

Two properties of that split are worth understanding, because they explain the machine's behavior in odd situations:

A missing verdict is a bad verdict. If the verdict is absent or more than two seconds old, a controller treats it as fire blocked, hold. The engine going away looks exactly like a fault, never like permission.

Arming requires being seen. The engine only grants fire when it is receiving fresh job reports. A controller about to fire is, by contract, one that is reporting — an armed window the engine cannot see never gets a green light.

If a controller goes silent past five seconds, the engine blocks fire immediately and stands the machine down through the normal cooldown, because a smoke clear is the right physical response to a job that died mid-cut. If the silence happens while the laser is armed, or while the pulse engine still says a program is playing, the engine additionally stops motion and locks the laser latch itself. It also refuses to let exhaust and intake drop below cooldown duty while a program is still running.

A cloud job brings its own envelope. The pulse file the Glowforge service sends opens with the job's operating limits, and the cloud client hands the ones the engine has a use for along with every report: the coolant window and the fans' minimum speeds. The engine takes each only where it is stricter than the setting on the Machine tab: a ceiling can only come down for a job, a floor can only go up, a looser value is noted in the log and ignored, and a gate you turned off (§8a) stays off whatever the job says. The coolant ceiling is the one limit a job can tighten today (the service sends 33 °C on a cut, which is also the shipped default); the fan floors are carried and logged ahead of the airflow gates. The effective set shows in the log as effective limits: and in /cool/status as limits. A GRBL job has no header and runs on the settings alone.

If a diagnostic takes the hardware over (§6), the engine suspends its own writes and publishes fire-blocked until the diagnostic finishes.

If the engine itself is provably gone while the laser is armed, the controller writes the factory run duties to the fans once, holds the job, and stands down. That is the single sanctioned exception to single-owner control, and the duties are compiled in so that a lost configuration file cannot take the fans with it.


3. What the fans do, and when

The engine runs in phases. Duties are the factory machine's own values.

Phase Pump Air assist Exhaust Intake Heater
Idle on 204 off off off
Run (or armed, whatever the reported mode) on 1023 65535 43278 flow checks only
Cooldown — smoke clear (15 s) on run duty run duty run duty off
Cooldown — thermal on idle 32768 21639 off
Over-temp / fault hold on run duty forced forced off

Notes on the phases:

  • The pump runs whenever the machine is on, including at idle. Circulation is cheap; a stagnant loop with a warm tube is not.
  • The heater is off at idle by design. An always-on flow heater measurably warms the loop within minutes, eating headroom below the start gate for no benefit while nothing can fire.
  • Being armed counts as running. If the laser is armed, the engine forces the run profile and the flow checks regardless of what mode the controller reported — fire never happens without cut airflow and active flow verification.
  • Cooldown has two stages: a smoke clear at full run duty, then reduced airflow (the radiator cools the loop measurably) until the upstream coolant temperature is back under the resume gate or the cooldown budget expires.
  • The TEC is left off. Its output has no readback, so the machine cannot tell whether one is fitted; driving it blind is not something ForgeFIRM does (see §9).

In GRBL mode the run profile follows your sender's M8/M9 (LightBurn's per-layer Air Assist), OR'd with the armed window. In cloud mode the job's own header carries the duties and the client passes them through, so a print gets the fan profile the service designed for it and a lens hunt stays quiet.

3a. Airflow gates: a fan that is not moving the air

Commanding a fan and getting airflow are two different things, and the machine can tell them apart: the exhaust, the two intakes and the air assist carry tachometers, and the purge-air fan in the head reports its current. While the run profile is applied, the engine holds every one of them to a floor.

  • The floors are settings (§8): cool_tach_exhaust_min_rpm, cool_tach_intake_min_rpm (either intake), cool_tach_air_assist_min_rpm and cool_purge_min_current, each 55 percent of the steady speed the fan reaches at the cut profile on the bench machine (exhaust 11640, intakes 4160, air assist 11050 rpm; the recommended bands are 50 to 60 percent). A cloud job's header can raise a tach floor for that job, never lower it (§2).
  • A fan is judged at the operating point its floor was measured at. While the laser is armed every fan is judged, and a job's own fan profile (a cloud header's run duties) may raise a fan above the cut profile but never lower it while armed. Unarmed, a fan is judged whenever it is commanded at or above the cut profile (a bare M8 from a GRBL job), and a fan the job runs slower is measured, published as unjudged, and not judged: the factory's hunts and homing moves run with the exhaust and the intakes off and the air assist at idle, and nothing can fire during them. The purge fan has no duty (it is always on) and is judged in every run.
  • A spin-up grace (cool_fan_grace_s) runs from the moment the run profile is written; nothing counts inside it, because the big exhaust fan takes seconds to reach speed.
  • Three seconds under the floor trip the gate, and a single reading at or above it in between clears the count, so a tach reading that wanders does not end a job.
  • A trip is a fault, not a pause. The verdict goes AIRFLOW, fire is blocked, the job holds, and there is no resume for the rest of that run session: a fan that has stopped moving air is not a condition to cut through. The fans stay at run duty (a stalled extraction fan needs every other fan around it running), and the reason names the fan, the reading and the floor. The fault ends with the session: at idle the verdict is OK again (a standing hold would cancel jogs and refuse the next job before it could re-prove the fan), and the next session judges every fan afresh after the grace.
  • A floor of zero is that gate off (§8a). It still measures: the first reading in a job that would have tripped the shipped default is logged.

/cool/status carries each fan's reading, floor and state (grace, ok, under, TRIPPED, off, unjudged for a fan the job runs below the cut profile unarmed, or idle outside a run) as fan_gates.


4. Coolant flow verification

The problem

A pump can stop, an impeller can slip, a line can airlock — and none of it shows up in a temperature reading until the tube is already in trouble. Absolute coolant temperature only tracks a loop that is circulating, and "coolant should warm up while cutting" is not a usable signal either: a light engrave may add no measurable heat at all.

The method

The small heater sits between the two thermistors. Each check runs it at a fixed duty for a fixed window and watches how far the downstream sensor climbs:

  • flowing coolant carries that heat away — the downstream sensor rises a little;
  • a stagnant loop cooks the sensor — the downstream sensor rises a lot.

The discriminator is the rise, not the difference between sensors, and the operating point is measured rather than assumed:

Parameter Value Why
Heater duty 40 % Below about 40 %, natural convection sheds the heat well enough to mimic flow — dead-pump trials have looked healthier than a working pump. At 40 % heat input outruns convection, and it is the cheapest duty that does.
Window 50 s Long enough for the bands to separate cleanly.
Fault threshold 14.4 °C rise Midway between the observed flowing band and the observed stagnant band.
Re-check interval 150 s A pump that stops mid-job is invisible otherwise.

Each check costs the loop under a degree of heating, and with cut-profile fans running the loop still nets cooler over a long job.

Checks start from a settled loop

Measuring a rise from a baseline captured while the loop is still cooling from earlier heat produces garbage — and it fails in the dangerous direction: it can report flow with the pump stopped. So a check is requested, and starts only once the two sensors agree within 1.5 °C and the downstream reading has stopped drifting.

Stationarity is judged by comparing the mean of the first half of a 15-second window against the second half, not by peak-to-peak spread. On a settled loop, peak-to-peak noise is about 0.5 °C while the split-half difference is about 0.1 °C — any peak-to-peak threshold tight enough to catch real drift would sit below the noise floor and never open the gate.

One bad reading is a suspicion, not a fault

Transients happen: cycling the pump by hand can burp an airlock that clears itself within minutes. So the engine runs a two-step decision:

  1. First over-limit check → COOLANT FLOW SUSPECT. A warning, a hold request, and an immediate re-check — no waiting for the normal cadence.
  2. The next completed check decides. Over-limit again, with no clean check in between → COOLANT FLOW FAULT. Clean → the suspicion clears and the job continues.

Two more rules close the loopholes:

  • A suspicion that cannot resolve escalates. If no verdict can be produced within the confirmation budget (default 480 s), it becomes a fault: a loop that will not settle after a fault-level reading has shown no evidence of health.
  • Cleared suspicions still count. Three of them in one job earn an aggregated "check your coolant" warning; the counter resets when cooldown reaches idle.

A clean check from the fault state logs a recovery.

What the verdicts do

Verdict Effect
OK Fire permitted.
SUSPECT Hold requested, cut airflow held; auto-resumes on a clean re-check.
FAULT Fire gated and the hold stands — for the operator to resolve.
OVERTEMP Hold with forced cooling airflow; auto-resumes below the resume gate (§5).
CRITICAL The coolant at or over the critical line in a run session: fire blocked, hold, no resume this job (§5).
AIRFLOW A fan under its floor: fire blocked, hold, no resume this job (§3a).
FIRE Motion stopped, latch locked, hold until the next run session (§7).

Practical note: expect a legitimate suspicion on the first checks after manually stopping and starting the pump. That is an airlock, the machinery above absorbs it, and it clears on its own.


5. Over-temperature

The engine uses the factory's coolant windows:

  • Run ceiling 33 °C — above this, the verdict goes OVERTEMP with a hold request and cooling airflow forced on.
  • Resume gate 31 °C — below this, recovery is signaled and the controller resumes automatically.
  • Critical line 38 °C (cool_temp_critical_c, §8) — a second tier above the ceiling, and a different kind: at or over it during a run session the verdict goes CRITICAL, fire is blocked, the job holds, and there is no resume for the rest of that session, because a loop that ran through the pause tier and kept climbing is not a condition to cut through. The fault ends with the session; the ceiling's pause keeps holding while the loop is hot, and the next session judges the line afresh. A cloud job's header carries no critical line for the coolant, so this one is always the local setting; the settings API keeps it above the ceiling while the ceiling is a gate (a ceiling at its off end leaves the line standing alone), and at its top (70 °C) it is the gate turned off (§8a).

The upstream sensor gates, because it reads the coolant actually entering the tube.

What you see depends on what the machine was doing. A running cycle takes a feed hold and resumes by itself once the loop recovers — your sender shows the hold state and a warning message. A jog is canceled instead (a jog cannot be held). Fire stays gated for the whole excursion.


6. Diagnostics: verifying and calibrating flow

The web panel's Diagnostics tab runs the two cooling tools. Both take the hardware over: the active controller is suspended for the duration, the engine stands aside, and the controller is restored on every exit path — completion, error, or your pressing Abort. The laser stays latched throughout. Progress, both coolant temperatures and a scrolling log stream to the page while it runs.

Both tools run at your configured duty, window and threshold, so the verdict applies to the check the machine actually performs, and both use cut-profile chassis fans — the condition the numbers were characterized under. Any pump-off window aborts immediately if the downstream sensor passes 48 °C.

Flow verify (about 3 minutes) — one check with the pump running and one with it commanded off.

  • PASS = your threshold separates the two readings.
  • Margins under 1.5 °C add a warning that you should re-calibrate.
  • A failure here means the threshold no longer suits the loop, or the loop has a real problem.

Flow calibrate (15–25 minutes) — three trials of each case, alternating, with settle gates between them. It reports both bands and recommends a threshold midway between the highest flowing reading and the lowest stagnant one, with an Apply button that writes it to your settings.

  • If the gap between the bands is under 3 °C it refuses to recommend anything and tells you to raise the heater duty and rerun.

When to calibrate: after replacing coolant, after changing or servicing the pump, if flow verify warns about thin margins, or if you see suspicions that you can trace to nothing real. The shipped default suits the factory loop; a rebuilt one may differ.


7. The fire watch

Alongside the flow work, the engine watches for evidence of things going wrong at one-second resolution:

  • Emission evidence. The kernel samples the gated output of the hardware AND-gate — actual emission, not a commanded state. Emission seen with no armed window in the recent past stops motion and locks the latch, and keeps doing so while the evidence persists.
  • Laser power-good degradation during an armed window is warned once per session.
  • Stepper-driver faults appearing during a run are warned, and HV current is ranged for each job in the same log line.
  • Lid infrared channels are polled every tick, and every job logs their baseline and peaks.

About the lid IR fire watch specifically: it ships in watch-only mode and logs rather than acts. The reason is honest and worth stating — those sensors are, first of all, a photometer for the lid lamp. A full-power cut raises them only a few counts above the level the lamp sets, a candle burning on the bed raises them about the same amount, and anything that changes the lamp (a camera snapshot, for instance) moves them by tens of counts. A fixed threshold would therefore stop jobs for lighting changes while still missing a small flame. A lamp-aware design is planned; until then the channels are recorded, not acted on, and the fire watch is not a fire alarm. Never leave a running laser unattended.


8. Settings

All of these live in the panel's Machine tab, are validated on entry, and can only be changed while the machine is idle. The engine re-reads them at the start of every run, so a change takes effect on your next job.

Setting Default Legal range Recommended What it controls
cool_flow_rise 14.4 °C 1 to 40 °C 8 to 16 °C Downstream rise that counts as no-flow. Set this from flow calibrate; above the band the check can never fault.
cool_flow_heater_pct 40 % 0 to 100 % Heater duty during a check. Raising it separates the bands further at the cost of warming the loop more.
cool_flow_check_s 50 s 0 to 300 s 30 to 120 s Length of a check window. 0 turns flow verification off (§8a).
cool_recheck_s 150 s 0 to 3600 s How often checks repeat during a job.
cool_confirm_max_s 480 s 60 to 3600 s How long a suspicion may stay unresolved before it escalates to a fault.
cool_temp_max 33 °C 5 to 60 °C 25 to 38 °C Run ceiling: above it, hold. 60 turns the gate off (§8a).
cool_temp_resume 31 °C 5 to 59 °C 20 to 36 °C Resume gate: below it, continue. Always kept below the ceiling.
cool_temp_critical_c 38 °C 6 to 70 °C 36 to 45 °C Critical line: a fault with no resume in the job (§5). Kept above the ceiling while the ceiling is a gate (a ceiling at 60 leaves the line standing alone); 70 turns the gate off.
cool_cooldown_s 15 s 0 to 1800 s Smoke-clear phase at run duty after a job.
cool_cooldown_max_s 300 s 0 to 1800 s Cap on the thermal cooldown phase.
cool_tach_exhaust_min_rpm 6400 rpm 0 to 20000 5800 to 7000 Exhaust fan floor at run duty (§3a). 0 turns the gate off.
cool_tach_intake_min_rpm 2290 rpm 0 to 20000 2100 to 2500 Intake fan floor, either intake (§3a). 0 turns the gate off.
cool_tach_air_assist_min_rpm 6000 rpm 0 to 30000 5500 to 6600 Air-assist fan floor (§3a). 0 turns the gate off.
cool_purge_min_current 300 raw 0 to 1023 150 to 500 Purge-air fan current floor (the fan has no tachometer; about 1 off, about 630 on). 0 turns the gate off.
cool_fan_grace_s 15 s 0 to 120 s 5 to 30 s Spin-up window after the run profile is written, during which no floor counts.

Two settings are deliberately not on the panel:

  • cool_fire_ir_delta, the lid-IR fire gate (§7). It is 0, watch-only, and changing it by hand is not recommended until the watch is lamp-aware.
  • GFCOOL_* environment overrides exist for bench work; they win for the lifetime of the process and are not a normal operating path.

8a. Turning a gate off

The gates are settings, and the far end of a gate setting's range is the off switch: a coolant ceiling of 60 °C never trips, a check window of 0 s runs no flow verification at all, and a fan floor of 0 never trips. There is no other switch, and no list of names to get wrong. The ranges are wide on purpose: the shipped defaults and the recommended bands come from one bench machine, and a machine whose loop or sensors read differently changes the number rather than waiting for new firmware.

A gate that is off is not a gate that is forgotten. The panel flags any value outside its recommended band beside the field and says "this gate is OFF" at the far end; the Status tab shows a standing banner while any gate is off; the engine logs one line per gate setting at every run start, and with the ceiling off it still logs the first reading in a job that would have tripped the default. /status and /cool/status carry the off gates as gates_off. Nothing about it reaches the cloud service.

What no setting can reach: the hardware safety chain, the laser latch, the emission witness, the lid-IR fire watch, the controller-silence dead-man, and the motion-liveness gate. A machine with every thermal gate off still stops firing the moment its controller goes quiet; what it no longer does is hold a job for a stopped pump or an overheating loop. The banner says so.


9. Not implemented yet

Stated plainly so nobody counts on them:

  • Low-temperature gates and warm-up. The factory holds a job and warms the coolant when the loop is below roughly 16 °C, and refuses to fire at all near freezing. ForgeFIRM does not yet; a cold-room machine will start cutting at a temperature the factory would have waited out. Two settings — a hard floor and a warm-up gate — are planned.
  • TEC control. ForgeFIRM never drives the thermoelectric cooler. Presence cannot be detected (the output has no readback), so this will become a user setting plus a simple hysteresis around the factory's setpoints.
  • A fire watch that acts (§7).
  • Chassis, SoC and supply ceilings. Three temperatures are measured and not gated: the chassis LM75 and the SoC die in degrees, the supply sensor as a raw count, in /status as temps (with the kernel's CPU throttle state beside them), on the Status tab, and ranged over every job in one log line (temps this job: ..., naming a throttle if one happened). The SoC already guards itself (the kernel throttles the CPU at 85 C and powers the board off at 90 C on this part). A ceiling for each comes from that record once there is enough of it. The supply's conversion stays unverified by decision (its heatsink is not reachable with a thermometer while the machine runs), so its reading stays a raw count and any ceiling for it would be set in raw counts too.
  • Fan floors measured on more than one machine. The shipped floors are a fraction of one bench machine's run-duty speeds; a machine whose fans read differently sets its own (§8), and a floor of zero turns that gate off while it does.

10. Quick reference: what the machine does when

Situation Machine response
Idle Pump on, purge air on, fans at idle, heater off, TEC off.
Job starts (or the laser arms) Cut airflow, flow check requested once the loop is settled.
Flow check over limit, first time SUSPECT: warning, hold, immediate re-check.
Second consecutive over limit FAULT: fire gated, hold stands until you resolve it.
Suspicion unresolved past the budget Escalates to FAULT.
Three cleared suspicions in one job Aggregated "check your coolant" warning.
Upstream coolant above 33 °C OVERTEMP: hold + forced cooling; auto-resume under 31 °C.
Upstream coolant at or over 38 °C during a job CRITICAL: fire blocked, hold, no resume this job; the ceiling's hold stands until the loop is under 31 °C.
A fan under its floor inside the spin-up grace Nothing yet: the gate reads grace.
A fan under its floor for three seconds after the grace AIRFLOW: fire blocked, hold, no resume this job; fans held at run duty; the next job starts the gates fresh.
Purge-air current absent at run duty AIRFLOW, the same way.
A gate setting at its off end (ceiling 60 °C, check window 0 s) No verdict from that gate; a run-start log line, gates_off in /status, and a standing panel banner.
Job ends 15 s smoke clear at run duty, then reduced airflow until the loop is under the resume gate.
Controller stops reporting Fire blocked at once, stand-down through cooldown.
Silence while armed, or a program still playing Motion stopped and the latch locked by the engine itself.
Verdict file missing or stale The controller treats it as fire-blocked and holds.
Diagnostic running Engine suspends its writes and publishes fire-blocked.
Engine gone while armed Controller writes factory run duties once, holds, stands down.

See also

  • Motion and laser drive — arming, job phases, both controller modes.
  • Laser safety — the hardware chain the beam actually passes through.
  • LightBurn setup & operation — M8/M9 and air assist in practice.
  • forgectrl/docs/SERVICES.md — the machine-services contract, including the report and verdict channels in full.