The record read "power capacity is the open item" next to ana-ml2's ~600 W, which reads as a cause. It is not one. The trip and its timing are measured; the attribution to the training load is the operator's working read and the reason for the weekend triage. The observation that makes the single-load story incomplete on its own terms: a site-wide blackout is a larger blast radius than one GPU box accounts for. If ana-ml2's draw were the whole story, ana-nas, ana-wg and the public address would not have gone dark with it. Shedding seats may still be the right first move and it is cheap. That is not the same as having identified what loaded the circuit, and the distinction matters going into a triage that will act on it.
89 lines
4.6 KiB
Markdown
89 lines
4.6 KiB
Markdown
# `[2026-08-27]` Anaheim tripped a power breaker — and four guests including the NAS never came back
|
|
|
|
Site-wide outage. **ana-ml2 was down 1h58m** — power lost between **18:14:45 and 18:17:00 PDT**,
|
|
boot at **20:13:14** (the "~90 minutes" first recorded here was an estimate; the window is now
|
|
pinned by run 3c's training log and the hourly cron that never ran — see
|
|
[[2026-08-27-run3c-launch-count-reconstruction]]). **Operator-confirmed cause: a tripped power breaker**, not a
|
|
fault and not the tunnel. The discriminator that established scope: `ana-srv1`
|
|
(38.120.12.44:443, Anaheim's PUBLIC address) was dark **from the internet**, so it was not the
|
|
NH3↔ANA IPsec tunnel stranding NH3 — the site was not answering on any path. `ana-ml2` returned
|
|
with `up 1 min`, confirming a hard power event.
|
|
|
|
## ⚠ THE DURABLE FINDING — `onboot` was unset on four guests
|
|
|
|
pfi-pve came back and auto-started everything **except**:
|
|
|
|
CT109 ana-nas the storage SPOF
|
|
CT113 ana-wg the WireGuard remote-access path
|
|
CT112 ana-filebot
|
|
VM106 corviduo-dev
|
|
|
|
All four had `onboot` unset. **Recovery was manual and would have been manual every time** —
|
|
including for the NAS that postgres/PBS/cross-site-restic depend on, and the WireGuard host
|
|
that is the way in when the site misbehaves.
|
|
|
|
**FIXED, with dependency ordering** (operator-authorised):
|
|
|
|
CT109 ana-nas onboot=1 order=1,up=45 <- first; 45s for NFS to SERVE
|
|
CT113 ana-wg onboot=1 order=2 <- remote access before anything can fail
|
|
VM104/105 Mongo/Postgres order=3,up=60 (pre-existing)
|
|
VM102 ANA-Docker order=4 (pre-existing)
|
|
VM101 ANA-DC order=5,up=120 (pre-existing)
|
|
CT112 ana-filebot onboot=1 order=10
|
|
VM106 corviduo-dev onboot=1 order=10
|
|
|
|
Every guest on pfi-pve now auto-starts. ana-nas precedes the databases deliberately; the
|
|
`up=45` is for NFS to be *serving*, not merely for the container to be *running* — the exact
|
|
distinction that killed `rest-server` on ana-docker, which came up before the NAS existed,
|
|
found nothing to serve, and exited 255.
|
|
|
|
## ⚠ `/tank` came back DEGRADED — a disk is genuinely gone
|
|
|
|
tank DEGRADED, raidz2-0, 7 devices ONLINE
|
|
9477159196657038377 FAULTED was /dev/nvme4n1p1
|
|
errors: No known data errors
|
|
|
|
**Only 7 physical NVMe present where the pool expects 8** — checked, so not renumbering. One
|
|
drive did not re-enumerate. raidz2 carries two disks of parity; one is spent. Operator taking
|
|
it; chassis is a Supermicro AS-4125GS-TNRT2 with PCIe hot-plug slots, so a swap should not
|
|
need a power-down.
|
|
|
|
## ⚠ `/mnt/smithy` is manual by design — it will be missing after EVERY reboot
|
|
|
|
Not in fstab, and **deliberately so**: a cross-site NFS entry can hang boot on a GPU host, and
|
|
it is `soft` rather than `hard` because ana-ml2 is cross-site from that NAS and a hard mount
|
|
turns a link blip into unkillable D-state. Remount with the recorded spec, do NOT "fix" it into
|
|
fstab:
|
|
|
|
sudo mount -t nfs4 -o ro,soft,timeo=30,retrans=3,proto=tcp,vers=4.1 \
|
|
10.100.50.50:/volume1/smithy /mnt/smithy
|
|
|
|
Full rationale: [[2026-08-23-smithy-mount-ana-ml2]].
|
|
|
|
## Power capacity is now the open item
|
|
|
|
Operator: *"we'll triage this weekend, probably shut down some seats."* ana-ml2 alone was
|
|
pulling ~600 W across both GPUs at their 300 W caps during training. `gen` stays up by
|
|
instruction; everything else on that box is idle.
|
|
|
|
⚠ **Keep the measured and the hypothesised apart here — the load attribution is NOT established:**
|
|
|
|
MEASURED a breaker tripped (operator-confirmed)
|
|
MEASURED power lost between 18:14:45 and 18:17:00 PDT
|
|
MEASURED the WHOLE Anaheim site went dark from the internet
|
|
|
|
HYPOTHESIS the training load tripped it — the operator's working read and the reason
|
|
for the weekend triage. There is no per-circuit meter on that panel, and
|
|
a site-wide blackout is a larger blast radius than one GPU box's ~600 W
|
|
accounts for on its own: if ana-ml2's draw were the whole story, why did
|
|
ana-nas, ana-wg and the public address go dark with it?
|
|
|
|
**Held as the right thing to triage first, not as the cause.** Shedding GPU seats may well be
|
|
correct and is cheap; it is not the same as having identified what loaded the circuit.
|
|
|
|
## Blast radius beyond us
|
|
|
|
heid lost **both gateway-routed arms of a four-arm panel** mid-dispatch and discovered the
|
|
outage by losing half a panel. That report produced the single most valuable artifact of the
|
|
incident — see [[2026-08-27-empty-response-as-a-datum]].
|