cooling.fans-quiet-after-motion sat silent for four minutes on the bench and then failed. Its idle reference was the tachs one second after the baseline saw the engine go idle, while the previous test's fans were still coasting at the cooldown level (exhaust 5030 rpm against a true idle of 0), so it then waited for the fans to come back UP to a level that was never idle. The cooldown wait printed nothing while it waited. The reference now needs the engine idle, the idle duty applied to both fan channels, and three consecutive tach samples that agree; the pass condition is the idle duty back and the tachs at or below that reference (lower is quieter, never a fault); M8 must visibly raise the duty; and every sample of both waits is logged with the phase and the duty, so the run pane shows the fans coasting down rather than a hang. Proof: tests/test_cooling_suite.py replays the test under the real Context against a scripted machine (fake forgectrl, fake sysfs duties, fake Grbl port): an idle machine passes, the bench case (fans coasting when the test starts) passes with the reference taken after the coast, fans left on fail with the reference in the message, and a reference that never settles fails before anything is jogged. No catalog consequence beyond the suite module's own hash.