The coolant critical tier, with its catalog test
forgectrl pin a1875a8: cool_temp_critical_c (default 38 C) is the fail tier above the coolant ceiling's pause: at or over it in a run session the verdict is CRITICAL (fire blocked, hold, no resume this job), the fault ends with the session, the settings API keeps it above the ceiling, and its top turns the gate off. Catalog: cooling.critical-tier (auto, 45 tests), driven through the settings API like cooling.gate-off: a critical line at the ceiling is refused (and undone should it ever be accepted); with the ceiling, the resume gate and the critical line all under the coolant's temperature a session reads CRITICAL rather than OVERTEMP with no resume and the reason naming the tier and the coolant; after the session the ceiling alone holds (OVERTEMP); with the critical line at its top the gate is off (gates_off, the run-start log line) and the ceiling alone pauses; restored, OK with nothing off. Four unit cases against a scripted engine. _after_session takes the condition to wait for. Docs: COOLING (verdict table, section 5, the settings table, the quick reference), BRINGUP item 19 and the catalog count, the CAMPAIGN-LOG paragraph for the fan-fault session rule on dev image 20260822145201.
This commit is contained in:
@@ -261,6 +261,8 @@ A clean check from the fault state logs a recovery.
|
||||
| `SUSPECT` | Hold requested, cut airflow held; auto-resumes on a clean re-check. |
|
||||
| `FAULT` | Fire gated and the hold stands — for the operator to resolve. |
|
||||
| `OVERTEMP` | Hold with forced cooling airflow; auto-resumes below the resume gate (§5). |
|
||||
| `CRITICAL` | The coolant at or over the critical line in a run session: fire blocked, hold, no resume this job (§5). |
|
||||
| `AIRFLOW` | A fan under its floor: fire blocked, hold, no resume this job (§3a). |
|
||||
| `FIRE` | Motion stopped, latch locked, hold until the next run session (§7). |
|
||||
|
||||
Practical note: **expect a legitimate suspicion on the first checks after
|
||||
@@ -277,6 +279,16 @@ The engine uses the factory's coolant windows:
|
||||
request and cooling airflow forced on.
|
||||
- **Resume gate 31 °C** — below this, recovery is signaled and the controller
|
||||
resumes automatically.
|
||||
- **Critical line 38 °C** (`cool_temp_critical_c`, §8) — a second tier above
|
||||
the ceiling, and a different kind: at or over it during a run session the
|
||||
verdict goes `CRITICAL`, fire is blocked, the job holds, and there is no
|
||||
resume for the rest of that session, because a loop that ran through the
|
||||
pause tier and kept climbing is not a condition to cut through. The fault
|
||||
ends with the session; the ceiling's pause keeps holding while the loop is
|
||||
hot, and the next session judges the line afresh. A cloud job's header
|
||||
carries no critical line for the coolant, so this one is always the local
|
||||
setting; the settings API keeps it above the ceiling, and at its top
|
||||
(70 °C) it is the gate turned off (§8a).
|
||||
|
||||
The **upstream** sensor gates, because it reads the coolant actually entering
|
||||
the tube.
|
||||
@@ -368,6 +380,7 @@ start of every run, so a change takes effect on your next job.
|
||||
| `cool_confirm_max_s` | 480 s | 60 to 3600 s | | How long a suspicion may stay unresolved before it escalates to a fault. |
|
||||
| `cool_temp_max` | 33 °C | 5 to 60 °C | 25 to 38 °C | Run ceiling: above it, hold. `60` turns the gate off (§8a). |
|
||||
| `cool_temp_resume` | 31 °C | 5 to 59 °C | 20 to 36 °C | Resume gate: below it, continue. Always kept below the ceiling. |
|
||||
| `cool_temp_critical_c` | 38 °C | 6 to 70 °C | 36 to 45 °C | Critical line: a fault with no resume in the job (§5). Always kept above the ceiling; `70` turns the gate off. |
|
||||
| `cool_cooldown_s` | 15 s | 0 to 1800 s | | Smoke-clear phase at run duty after a job. |
|
||||
| `cool_cooldown_max_s` | 300 s | 0 to 1800 s | | Cap on the thermal cooldown phase. |
|
||||
| `cool_tach_exhaust_min_rpm` | 6400 rpm | 0 to 20000 | 5800 to 7000 | Exhaust fan floor at run duty (§3a). `0` turns the gate off. |
|
||||
@@ -440,6 +453,7 @@ Stated plainly so nobody counts on them:
|
||||
| Suspicion unresolved past the budget | Escalates to `FAULT`. |
|
||||
| Three cleared suspicions in one job | Aggregated "check your coolant" warning. |
|
||||
| Upstream coolant above 33 °C | `OVERTEMP`: hold + forced cooling; auto-resume under 31 °C. |
|
||||
| Upstream coolant at or over 38 °C during a job | `CRITICAL`: fire blocked, hold, no resume this job; the ceiling's hold stands until the loop is under 31 °C. |
|
||||
| A fan under its floor inside the spin-up grace | Nothing yet: the gate reads `grace`. |
|
||||
| A fan under its floor for three seconds after the grace | `AIRFLOW`: fire blocked, hold, no resume this job; fans held at run duty; the next job starts the gates fresh. |
|
||||
| Purge-air current absent at run duty | `AIRFLOW`, the same way. |
|
||||
|
||||