The fan floors proven on a pinned image; a fan fault ends with its session
The dated record of dev image 20260822135848: the campaign of every non-operator, non-live test at 18 of 18 PASS with the measured floors and the operating-point rule (cooling.fan-gate-trips and the hunt leg of cloud.mode-switch as recorded), and the unplugged-exhaust-fan drill: AIRFLOW at the grace plus three ticks with the exhaust dead, the other fans held, the reason relayed on the Grbl port, the replugged fan ok inside the next session's grace. The drill showed the fault riding into idle, where the hold canceled jogs and would have refused the cloud print that re-proves the fan. forgectrl pin d51dbdb: the fault ends with its run session, and the next session judges every fan afresh. cooling.fan-gate-trips checks the verdict is OK with no hold once the tripped session is over (the unit fake mirrors it); its covers, and the cooling tests' shared covers, gain src/coolfmt.* (the tree manifest carries the new files at the bumped pin, and the lint was right to ask). cloud.mode-switch samples the hunt's gate rows twice a second: a hunt's run phase is a few seconds long. Docs: COOLING 3a, BRINGUP item 19, CAMPAIGN-LOG.
This commit is contained in:
+14
-6
@@ -1358,12 +1358,20 @@ Open items only. Anything closed is in `CAMPAIGN-LOG.md`.
|
||||
and unarmed whenever it is commanded at the run duty; a cloud hunt,
|
||||
sent with the extraction fans off, is measured and not judged.
|
||||
`cooling.fan-gate-trips` and the hunt leg of `cloud.mode-switch` in
|
||||
the catalog. The shipped floors are 55 percent of the bench machine's
|
||||
measured steady speeds (facts bank: exhaust 6400, intake 2290, air
|
||||
assist 6000 rpm, purge current 300, grace 15 s); the bench run of the
|
||||
gate tests on an image carrying them, and the unplugged-tach drill,
|
||||
are still owed. The coolant critical tier and the watch-only board
|
||||
temperatures follow.
|
||||
the catalog, both PASS on the pinned dev image `20260822135848`
|
||||
(campaign 18 of 18). The shipped floors are 55 percent of the bench
|
||||
machine's measured steady speeds (facts bank: exhaust 6400, intake
|
||||
2290, air assist 6000 rpm, purge current 300, grace 15 s). The
|
||||
unplugged-exhaust-fan drill PASS on the same image: `AIRFLOW` at
|
||||
grace plus three ticks with the exhaust dead, the other fans held,
|
||||
the reason relayed on the Grbl port, and the replugged fan `ok` inside
|
||||
the next session's grace (CAMPAIGN-LOG). From the drill: the fault
|
||||
ends with its run session (decided; a standing hold at idle canceled
|
||||
GRBL jogs and would have refused the cloud print that re-proves the
|
||||
fan), since every session judges every fan afresh after the grace;
|
||||
`cooling.fan-gate-trips` checks it, bench run owed on the next image.
|
||||
The coolant critical tier and the watch-only board temperatures
|
||||
follow.
|
||||
|
||||
Nothing here can put energy where it was not commanded: the hardware chain
|
||||
is the emission boundary and no header field touches it, and forgectrl runs
|
||||
|
||||