Fan floors from the measurement; a hunt is measured, not judged

forgectrl pin 47e4256: the airflow floors set from the bench measurement
(exhaust 6400, intake 2290, air assist 6000 rpm, purge current 300, grace
15 s) and the operating-point rule: a fan is judged while the laser is
armed, when a job's profile may raise it but never lower it below the run
duty, or whenever it is commanded at the run duty; the service's hunts,
sent with the extraction fans off, are measured and published unjudged.

Catalog: cloud.mode-switch now waits out the connect-time hunt sampling
/cool/status and requires no AIRFLOW, the exhaust row unjudged and the
exhaust actually off; its covers gain forgectrl src/cool.* and
src/airflow.*. cooling.fan-gate-trips uses an 8 s test grace (the
intakes take 7 s to 90 percent and tripped under the old 2 s at the new
floor) and its off leg waits for the row state as well as gates_off.
fan_floor_measure.py names a reply that is not JSON and calls the purge
readings idle and run (the pump is always on).

Docs: COOLING 3a and the settings table, BRINGUP item 19 and a facts-bank
entry with the measured fan speeds, the bench README, and a CAMPAIGN-LOG
entry for the measurement, the two status-document finds, the hunt find
and the hot-deployed bench runs of both tests.
This commit is contained in:
ScottW514
2026-08-22 09:56:53 -04:00
parent 71a79b6675
commit adcd1adb9a
9 changed files with 165 additions and 32 deletions
+54
View File
@@ -3254,6 +3254,60 @@ value), and the test quoted the session's first job-limits line, a hunt's,
where the print's is the one worth keeping (it now takes the first line
after the print's action request).
## 2026-08-22: the fan floors measured, and a hunt that would have tripped them
`fan_floor_measure.py spinup` (bench page `fan-floor`, 120 s at the cut
profile from idle, GRBL mode, the exhaust duct's inline booster fan off, so
the exhaust worked against more back pressure than a normal cut):
| fan | steady rpm | min | max | sd | t90 |
|---|---|---|---|---|---|
| exhaust | 11638 | 11444 | 11947 | 103 | 5 s |
| intake 1 | 4157 | 4102 | 4193 | 12 | 7 s |
| intake 2 | 4158 | 4128 | 4173 | 6 | 7 s |
| air assist | 11048 | 11029 | 11061 | 8 | 1 s |
Purge current 627 at idle and 625 at run duty: the engine holds purge air on
continuously, so both are the "on" reading (the off reading, ~1, is from an
earlier observation). The floors shipped from this: exhaust 6400, intake
2290, air assist 6000 rpm (55 percent of steady, bands 50 to 60 percent),
purge current 300, grace 15 s (twice the slowest time to 90 percent). The
provisional floors had come from a snapshot at a lower exhaust speed; the
measured margin is larger.
The run also sent the first `/cool/status` with the limits and the fan rows
through a 512-byte reply buffer, and then a 160-byte limits fragment: twice
a cut-off document, found by the measurement tool refusing to parse it.
Both fixed in forgectrl with a host test that renders the widest legal
document and parses it (`tests/coolfmt_test.c`).
Reading the measurement through cloud mode found a defect in the gates as
first built: the service reports every action as a run, and its hunt and
motion headers command the exhaust and the intakes off and the air assist
at idle, so a hunt longer than the grace would have tripped `AIRFLOW` at
any floor. Decision (operator): a fan is judged only at the operating
point its floor was measured at: always while the laser is armed, when a
job's profile may raise a fan but never lower it below the run duty; and
unarmed when commanded at the run duty. A hunt is measured, published as
`unjudged`, and not judged. `cloud.mode-switch` now watches the connect-time
hunt's gate rows for it.
Both tests ran the same day on a hot-deployed forgectrl (the working tree
cross-built and installed over dev image `20260821230723`; informational,
not acceptance). `cloud.mode-switch` PASS: the hunt reported two run ticks
with the exhaust off and `unjudged`, verdict `OK` throughout.
`cooling.fan-gate-trips` FAIL first, for two reasons worth keeping: the
run-start tick resolved the effective limits before it reloaded the
settings, so for one tick `gates_off` named the exhaust while its row still
carried the old floor (fixed: the session start re-resolves the limits after
the reload, so rows, `gates_off` and the log line agree); and the test's
2 s grace, chosen against the provisional 1800 rpm intake floor, now let
both intakes trip at ~1850 rpm on their 7 s spin-up (the test grace is 8 s).
Rerun PASS in 59 s: only the exhaust tripped in the exhaust leg, only the
purge in the purge leg, the exhaust read `off` with floor 0 in the off leg,
and the restore showed every fan `ok` at the shipped floors (exhaust 11723,
intakes 4157 and 4162, air assist 11078 rpm, purge 628 counts).