The critical tier proven on a rising loop; the board temperatures watched

forgectrl pin 76115fd: the chassis LM75 and the supply sensor ride /status
as temps (degrees and a raw count), the engine ranges them over every run
session into one run-end line, and a critical fault that clears with its
session yields the reason to the standing hold.

Bench: critical_tier_drill.py (a bench tool now, registered as
critical-tier) sets the ceiling, the resume gate and the critical line a
few tenths above the live upstream reading and lets the engine's own
flow-check heater warm the loop through them inside one M8 session;
temp_calibrate.py gains supply-watch, supply-point and supply-fit for the
supply sensor against a thermometer on its heatsink, the fit shown beside
UAPI.md's unverified guess.

Catalog: cooling.gate-off checks the /status temps fields and the run-end
board-temperature line (the unit fake mirrors both, one new failure
case); cooling.critical-tier checks the reason after a faulted session.

Docs: CAMPAIGN-LOG entries for cooling.critical-tier on dev image
20260822154257 and the warm-loop drill (OVERTEMP at 10 s, CRITICAL at
14 s, the fault ending with the session); BRINGUP item 19, the facts bank
(board temperatures at idle), COOLING section 9, the bench README.
This commit is contained in:
ScottW514
2026-08-22 12:56:40 -04:00
parent f51140e528
commit 9fae47cf14
10 changed files with 372 additions and 9 deletions
+34
View File
@@ -3368,6 +3368,40 @@ and flashed the same day (dev image `20260822145201`, forgectrl d51dbdb):
`cooling.fan-gate-trips` PASS in 60 s, the engine reading `OK`, no hold,
fire allowed in the smoke-clear phase right after the tripped session.
## 2026-08-22: the coolant critical tier, on an image and on a rising loop
Dev image `20260822154257` (forgectrl a1875a8 pinned by forgefirm f51140e):
`cooling.critical-tier` PASS in 23 s. As recorded: the settings API refused
a critical line equal to the ceiling (`400 cool_temp_critical_c must be
above cool_temp_max`) and changed nothing; with the ceiling at 6 C, the
resume gate at 5 C and the critical line at 7 C under 24.3 C coolant the
session read `CRITICAL` (`fire_ok false`, `hold true`, no `resume_ok`,
reason `CRITICAL: coolant 24.3 C at or over the 7 C critical line - hold,
no resume this job`); after the session the ceiling alone held
(`OVERTEMP`); with the critical line at its top of 70 the gate was off
(`gates_off` naming `coolant_critical`, the run-start log line) and the
ceiling alone paused; restored, `OK` with nothing off.
The physical drill, `critical_tier_drill.py`, the same day. The loop heater
reaches the high twenties at most, so the lines were set a few tenths
above the live upstream reading (24.57 C: ceiling 25.0, resume 24.8,
critical 25.3) and the engine's own flow-check heater (100 percent, 300 s
windows, rechecks every 30 s, the suspect threshold at its top) warmed the
loop through them inside one `M8` session. Transitions, as sampled once a
second: `OK` at 24.1 C; `OVERTEMP` at 10 s with the upstream at 25.05 C
(`coolant 25.0 C over 25 C limit - hold until 25 C`); `CRITICAL` at 14 s
at 26.24 C (`fire_ok false`, `hold true`, relayed on the Grbl port as a
`[MSG:Warning: CRITICAL: ...]`). `M9` ended the fault and the ceiling's
`OVERTEMP` stood in the smoke-clear phase (upstream 27.7 C, downstream
49.7 C from the heater, which the session end switched off). Settings
restored and re-read in a short session: `OK`, limits back to 33 / 31 / 38.
One find, cosmetic: after the session the reason text still read the
critical line's message under the ceiling's verdict, because the ceiling
names itself only on its rising edge and the critical fault had overwritten
it. The engine now re-publishes the standing hold's reason when a critical
fault clears (no new log line), and `cooling.critical-tier` checks it.