The critical tier proven on a rising loop; the board temperatures watched
forgectrl pin 76115fd: the chassis LM75 and the supply sensor ride /status as temps (degrees and a raw count), the engine ranges them over every run session into one run-end line, and a critical fault that clears with its session yields the reason to the standing hold. Bench: critical_tier_drill.py (a bench tool now, registered as critical-tier) sets the ceiling, the resume gate and the critical line a few tenths above the live upstream reading and lets the engine's own flow-check heater warm the loop through them inside one M8 session; temp_calibrate.py gains supply-watch, supply-point and supply-fit for the supply sensor against a thermometer on its heatsink, the fit shown beside UAPI.md's unverified guess. Catalog: cooling.gate-off checks the /status temps fields and the run-end board-temperature line (the unit fake mirrors both, one new failure case); cooling.critical-tier checks the reason after a faulted session. Docs: CAMPAIGN-LOG entries for cooling.critical-tier on dev image 20260822154257 and the warm-loop drill (OVERTEMP at 10 s, CRITICAL at 14 s, the fault ending with the session); BRINGUP item 19, the facts bank (board temperatures at idle), COOLING section 9, the bench README.
This commit is contained in:
@@ -3368,6 +3368,40 @@ and flashed the same day (dev image `20260822145201`, forgectrl d51dbdb):
|
||||
`cooling.fan-gate-trips` PASS in 60 s, the engine reading `OK`, no hold,
|
||||
fire allowed in the smoke-clear phase right after the tripped session.
|
||||
|
||||
## 2026-08-22: the coolant critical tier, on an image and on a rising loop
|
||||
|
||||
Dev image `20260822154257` (forgectrl a1875a8 pinned by forgefirm f51140e):
|
||||
`cooling.critical-tier` PASS in 23 s. As recorded: the settings API refused
|
||||
a critical line equal to the ceiling (`400 cool_temp_critical_c must be
|
||||
above cool_temp_max`) and changed nothing; with the ceiling at 6 C, the
|
||||
resume gate at 5 C and the critical line at 7 C under 24.3 C coolant the
|
||||
session read `CRITICAL` (`fire_ok false`, `hold true`, no `resume_ok`,
|
||||
reason `CRITICAL: coolant 24.3 C at or over the 7 C critical line - hold,
|
||||
no resume this job`); after the session the ceiling alone held
|
||||
(`OVERTEMP`); with the critical line at its top of 70 the gate was off
|
||||
(`gates_off` naming `coolant_critical`, the run-start log line) and the
|
||||
ceiling alone paused; restored, `OK` with nothing off.
|
||||
|
||||
The physical drill, `critical_tier_drill.py`, the same day. The loop heater
|
||||
reaches the high twenties at most, so the lines were set a few tenths
|
||||
above the live upstream reading (24.57 C: ceiling 25.0, resume 24.8,
|
||||
critical 25.3) and the engine's own flow-check heater (100 percent, 300 s
|
||||
windows, rechecks every 30 s, the suspect threshold at its top) warmed the
|
||||
loop through them inside one `M8` session. Transitions, as sampled once a
|
||||
second: `OK` at 24.1 C; `OVERTEMP` at 10 s with the upstream at 25.05 C
|
||||
(`coolant 25.0 C over 25 C limit - hold until 25 C`); `CRITICAL` at 14 s
|
||||
at 26.24 C (`fire_ok false`, `hold true`, relayed on the Grbl port as a
|
||||
`[MSG:Warning: CRITICAL: ...]`). `M9` ended the fault and the ceiling's
|
||||
`OVERTEMP` stood in the smoke-clear phase (upstream 27.7 C, downstream
|
||||
49.7 C from the heater, which the session end switched off). Settings
|
||||
restored and re-read in a short session: `OK`, limits back to 33 / 31 / 38.
|
||||
|
||||
One find, cosmetic: after the session the reason text still read the
|
||||
critical line's message under the ceiling's verdict, because the ceiling
|
||||
names itself only on its rising edge and the critical fault had overwritten
|
||||
it. The engine now re-publishes the standing hold's reason when a critical
|
||||
fault clears (no new log line), and `cooling.critical-tier` checks it.
|
||||
|
||||
## Superseded status notes
|
||||
|
||||
### Shared machine services — remaining polish, as listed 2026-08-13
|
||||
|
||||