vh 3180dc85fa memory: snapshot — Ada sizing corrected; prune and drives are orthogonal
comfy-dev's disk-vs-catalog diff and a recount of my own figures both
landed on this thread. Two numbers were wrong and both were headed for
the operator's sizing conversation.

- My ~90% was a double-count. I read ALLOC 1.45T while their pull was
  running and then added the full ~112 GB on top; most of it was already
  in that reading. "Onboarded" is not "landed". Settled payload is
  ~1.47 TiB and the as-bought mirror lands at 84%, not 90%.
- comfy-dev's "pruning gets us nearer 45%" is the striped figure. On the
  as-bought pair mirrored, deleting all ~215 GiB of unreferenced weights
  still lands at 72%, with ~140 GiB of runway on a store that took on
  ~100 GiB in one day. The constraint is vdev layout, not payload — a
  1.75 TiB pool stays 1.75 TiB whatever goes in it.
- So the prune audit and the drive purchase are independent decisions
  and neither gates the cutover. Presenting them to the operator that
  way rather than as a trade.

Also recorded: pool arithmetic (1.75 / 3.49 / 3.57 TiB), the mirror-vdev
smallest-member gotcha if the new drives get paired one-each with the
1.92s, comfy-dev's 34 GiB of uncatalogued LTX 2.5, and an open question
back to them on whether the H3 encoder's nvfp4 pin was set under a
Blackwell assumption that sm_89 does not satisfy.

Memory-only; no version bump per the SemVer SKIP list.
2026-09-01 17:11:04 -07:00

7.2 KiB
Raw Blame History

[2026-09-01] The Ada inference server is a Dell R750xa bought used — and the reseller stripped four things Dell shipped

Dell PowerEdge R750xa, service tag JPJ1ZP3, 8-bay 2.5" 2U. Bought from Entera Source (invoice INV-74422, 2026-08-25). 2× NVIDIA RTX 6000 Ada 48 GB to be fitted — confirmed by the operator, NOT L40/L40S. Destination NH3. This is ComfyUI's new home; the GX10 is a separate machine → 2026-09-01-pfi-gx10-onboarding.

As bought

CPU      2x Xeon Silver 4314   16C/32T each = 32C/64T, 135 W each
RAM      8x Micron 16 GB PC4-3200 = 128 GB
NIC      dual 25 GbE SFP28 (Broadcom 57414, OCP 3.0)
boot     BOSS-S2 + 2x 240 GB M.2 SATA, mirrored
storage  2x 1.92 TB SATA SSD (Hynix), 6 of 8 bays free
HBA      PERC HBA355i (LSI SAS3816)
PSU      2x 1400 W Platinum

THE DIFF — factory CSV (JPJ1ZP3.csv, booth 54-puffin) vs the invoice

Dell factory reseller invoice
RAM 16× 16 GB M04W6, "Performance Optimized" = 256 GB 8× = 128 GB
PSU 2400 W redundant (450-AJEV) 2× 1400 W (7DWXY)
GPUs 4× Tesla V100-32GB passive (490-BHUC) none
GPU risers 12XPY (right DW), 9TR6X (left DW) not listed
GPU cables 470-AEVS 4-GPU kit: 4RW1P W4K7M XC48N 6C77X not listed
Riser cables signal CP67W CXYF8 H4D7D N61TK; power HXJDR W1P56; pad C2JNP not listed
Fans 6× FD00R Very High Performance not listed
Controller PERC H345 HBA355i — an UPGRADE for us
Drives 2× 480 GB 2× 1.92 TB

"Not listed on the invoice" is not proof of removal. Operator will pull an iDRAC inventory to settle it. Diff that against the CSV rather than the invoice.

The GPU power chain — resolved, and my first answer was wrong

RTX 6000 Ada: 300 W, ACTIVE cooling, one 16-pin 12VHPWR (CEM5) connector (nvidia.com).

The R750xa kit 470-AEVS is "W/CPU CONN" — CPU/EPS 8-pin, because V100 takes that. I initially flagged this as a mismatch requiring the PCIe-type cable RCCWC / Dell 470-BBXH. That was wrong and is withdrawnRCCWC is for H100/L40/L40S.

NVIDIA sells the bridge for exactly this case:

930-00030-1546-000 — NVIDIA Power Cable, RTX 6000 Ada Generation, 1× CPU 8-Pin → 1× CEM5 16-Pin

So the chain is 470-AEVS CPU 8-pin → 930-00030-1546-000 → card. The chassis' existing cabling is the correct source type. Two adapters needed, one per card.

⚠ Factory brackets are VFYGM — the V100S extended bracket. RTX 6000 Ada is a different physical card; bracket fit is UNKNOWN, check at fitting.

Active cooling in a passive-card chassis. Six high-performance fans expect to push air through passive cards; the RTX 6000 Ada has its own blower. It works in practice, but Dell never validated this combination for this box.

Storage — NVMe in the drive bays is CLOSED

Factory backplane is 321-BGKG : 2.5" Chassis with up to 8 **SAS/SATA** Drives. Not NVMe-capable; bays would need a backplane swap.

Arithmetic if filling bays with SATA:

2x SATA (today)     ~1.1 GB/s
6x striped          ~3.3 GB/s      <- roughly ONE NVMe drive
8x striped          ~4.4 GB/s
backplane ceiling   ~6 GB/s (8 lanes x SATA III)

The HBA355i (PCIe 4.0 x8) is nowhere near limiting. Drives are the constraint.

ARC probably beats spindles here. ComfyUI reloads the same checkpoints; with the factory 256 GB restored, ZFS ARC caches most of the working set at RAM speed. The RAM upgrade is both cheaper and likely faster than four more SATA drives.

CAPACITY, not throughput, is the binding constraint — the as-bought drives are SMALLER than the pool they receive from (measured 2026-09-01). ComfyUI's /storetank on irv-ml1 is a 2x 2 TB mirror: SIZE 1.81 TiB, ALLOC 1.45 TiB, CAP 80%. Settled payload ~1.47 TiB. The R750xa's 2x 1.92 TB mirrored is only ~1.75 TiB — smaller than the source pool — so the migration arrives at ~84% full with no growth room, past the ~80% line where ZFS allocation degrades. Compression buys nothing: safetensors measured compressratio 1.00x, logicalused == used.

-> Add 2x 2 TB SATA SSD to the buy list. Six of eight bays free, HBA355i has the ports; two mirror vdevs = ~3.57 TiB at ~41%, redundancy intact. Cheapest line on this buy list and it does not gate the cutover window. The no-spend alternative is striping the as-bought pair (~3.49 TiB, no redundancy) — only acceptable if irv-ml1 retains its copy, which makes retain a requirement rather than a recommendation.

Pruning does NOT substitute for the drives. comfy-dev found ~215 GiB of unreferenced weights; deleting every byte still lands the as-bought mirror at 72%. The constraint is vdev layout, not payload — a 1.75 TiB pool stays 1.75 TiB whatever goes in it. The prune audit and the drive purchase are independent decisions.

Build-time: pair like with like. A mirror vdev caps at its smallest member; pairing each new 2 TB with an existing 1.92 TB caps both vdevs at 1.92 TB and wastes ~150 GiB. Correct: the two 1.92s as one vdev, the two new drives as the other. → 2026-09-01-ada-migration-branch-a

UNCHECKED, and it may moot the whole bay question: free PCIe slots. Riser Config 0 is 330-BBUM : Riser Config 0, 6x16 + 2x8 slots; two double-wide GPUs will not consume all of it. An NVMe add-in card (U.2 HBA or bifurcating M.2 carrier) bypasses the SAS/SATA backplane entirely. Add slot inventory to the iDRAC pull.

Power — the ceiling is deliberate now, not discovered later

2x RTX 6000 Ada   600 W
2x Xeon 4314      270 W
rest             ~150 W
               ~1,020 W sustained

One 1400 W PSU carries that, so redundancy holds. But factory specced 2400 W for four V100s: there is no headroom for a third or fourth GPU. And ~1 kW is the same class as ana-ml2, the box whose training run tripped a breaker on 2026-08-26 — decide which NH3 circuit this lands on before racking, not after.

Buy list

Certain:

item part qty
RDIMM 16 GB 3200 2Rx8 M04W6 8 → restores 256 GB, all 16 slots, all 8 channels/socket
NVIDIA 12VHPWR adapter 930-00030-1546-000 2
2 TB SATA SSD (any; match/exceed the MX500s) 2 → pool ~3.57 TiB at ~41%; without it the migration lands at ~84%. Pair the two NEW drives together, not one-each with a 1.92

Only if the iDRAC inventory shows them absent: 12XPY, 9TR6X, 4RW1P, W4K7M, XC48N, 6C77X, CP67W, CXYF8, H4D7D, N61TK, HXJDR, W1P56, C2JNP, FD00R ×6.

Spend order: RAM → 2 SATA SSDs (now certain, capacity-driven) → check PCIe slots → only then consider filling the remaining bays. (The original order deprioritised drives on a throughput argument, which still holds; the drives are now on the certain list for capacity, which is a different axis.)

⚠ Dell's Installation & Service Manual publishes no part numbers at all for GPU kit hardware — names and quantities only. The factory CSV keyed to the service tag is the only authoritative source of DPNs for this machine. Do not accept a five-character DPN from anywhere else without corroboration.