# `[2026-09-13]` STANDING POLICY (operator): cap GPU power limits at BUILD time, not after discovering the constraint. ⭐ **STANDING POLICY (operator): cap GPU power limits at BUILD time, not after discovering the constraint.** ⭐ **Two DIFFERENT boxes, clarified by operator 2026-09-13:** **fv-ml1** = 4x **Blackwell** RTX PRO 6000 **Max-Q @ 300 W** (Max-Q is the reduced-TGP SKU; Workstation Edition is 600 W), 391 GB VRAM, deployed. **ana-ml3** = 2x **Ada Generation** RTX 6000 @ 300 W, 96 GB VRAM, **NOT YET DEPLOYED**. **CAPS: fv-ml1 → 250 W/card (83% of TGP, ~5% throughput cost); ana-ml3 → 200 W/card (67%, ~10-15%).** ⚠⚠⚠ **`nvidia-smi -pl` caps BOARD power, not WALL power** — 4x250 = 1000 W board + ~180-300 W host components = 1180-1300 W, ÷ ~0.90 PSU efficiency = **~1310-1445 W AT THE PLUG vs a 15 A circuit's 1440 W NEC continuous limit. 250 W lands ON the line, not under it** (200 W would give ~1090-1220 W, comfortable). **Procedure: set 250 W, then VERIFY at the plug under four-card load; fall back to 200 W if it reads near 1440 W.** ⚠ Caps bound SUSTAINED draw, not transients — breakers tolerate brief overload, UPS overload protection does not, so 250 W implicitly commits the fv-ml1 chassis to the PDU rather than behind the 1500 VA unit (even capped it exceeds that UPS). ⭐ **BANK-level cap asked about and answered:** `DCGM_CONFIG_POWER_BUDGET_GROUP` ("power budget for the entire group") exists alongside `DCGM_CONFIG_POWER_CAP_INDIVIDUAL`, but the docs do not say how it distributes — and the only primitive underneath is NVML's PER-GPU `nvmlDeviceSetPowerManagementLimit` (**no bank-level register**), so any group budget resolves to N per-GPU writes. "Each card free until all are loaded" is therefore a CONTROL LOOP, not a hardware feature. ⚠⚠ If one is written it must be **safe-by-default, opportunistic upward** — boot at budget/N and only RAISE after observing idle neighbours; a reactive loop overshoots during a load RAMP, which is the all-cards-at-once case it exists to prevent. **Not yet worth it: 4x250 = 1000 W IS the bank budget**, so the daemon's whole prize is the one-card-busy case (~17% more board power ≈ ~5% throughput) — rare for a SERVING fleet (one seat per card), valuable for a TRAINING window. **DCGM** = NVIDIA's first-party **Data Center GPU Manager** (Apache-2.0), layered ABOVE NVML: nvidia-smi → NVML per-GPU primitives → DCGM daemon/dcgmi for health, diagnostics, config enforcement, groups. ✅ **VERIFIED 2026-09-13 (I had claimed the opposite and was WRONG): DCGM SUPPORTS our cards and power config works on them.** Supported platforms cover *"All NVIDIA Maxwell and newer NON-DATACENTER (e.g. GeForce or Quadro) GPUs"*, and the feature-overview table marks **Configuration Management ✓ for Tesla/Titan/Quadro/GeForce alike** — including *"Power Limit: set the maximum allowed power consumption"*. What IS gated on non-datacenter cards is **diagnostics** (Level 1 only vs All Levels on Tesla), not config. ⚠ Soft edge: the table says "Quadro", the former professional-line name; RTX 6000 Ada / RTX PRO 6000 are its successors and should fall in that column, but the table predates the rename — one command on the box settles it. ⭐ So the group-budget test IS worth running; what remains unsettled is *distribution*, not availability. ✅ **The static cap needs none of it**: `nvidia-smi -pl 250` is plain NVML and works on these cards; DCGM is probably not even installed (beszel-agent-nvidia shells out to nvidia-smi). ⚠ ana-ml3's 200 W on 2 cards (2x200 = 400 W) — and ⭐ ana-ml3 lands in the **Anaheim** rack whose breaker tripped 2026-08-26 and 2026-09-11, one of those caused by this very chassis before it relocated, so the cap there is remediation of a known-bad circuit, not precaution. 4x200 W = 800 W of card, which fits a real circuit with a real UPS. This is the generalised lesson of the FV outage: decide the power envelope first and size the cards into it. At 300 W TGP, 200 W is a **67% cap — the favourable part of the concave perf/watt curve, ~10-15% throughput cost**, not the severe 33% cap a 600 W part would have meant; and 200 W is very unlikely to sit below a 300 W card's enforceable floor (still confirm with `nvidia-smi -q -d POWER | grep -iE 'power limit|default'`). ⭐⭐ **The outage arithmetic now has numbers:** 2x Blackwell Max-Q @300 W ≈ 600 W of card + host (566 GB RAM, drives, fans, PSU losses) ≈ 200-350 W = **~800-950 W against a 1500 VA Eaton's real ~900-1200 W rating** — at or just over the line, which is what explains a full day on ONE card (~500-650 W, inside) and death minutes into the SECOND. The host term is the only guess; idle-at-the-plug measures it. ⚠⚠ **And FOUR cards is a BREAKER problem, not a UPS problem:** 4x300 + ~300 host ≈ **1500 W vs a 15 A circuit's 1440 W continuous (80%) derating** — so **capping belongs at fv-ml1 too**, or it needs a 20 A feed, before anyone loads all four cards again. Today's incident only ever had TWO cards working. ⭐ **Decode tolerates caps far better than training** (memory-bandwidth-bound, concave curve). ⚠⚠ **ana-ml3's Ada is sm_89: native FP8 but NO NVFP4** (Blackwell-only) — most of our in-house quants are NVFP4 and will NOT run accelerated there; ana-ml3's seats want FP8 W8A8, or NVFP4 checkpoints stay on fv-ml1. ⭐ **This unparks [[parked_triton_backend_ampere_fp8]]** — a hard no on Ampere (fp8e4nv unsupported sm_86), explicitly deferred TO Ada, and sm_89 has the FP8 support it needs. **ana-ml3 VRAM is 2x48 = 96 GB** vs fv-ml1's 391 GB, so big-model placement stays at FV (Flash-Next needs 74 GiB resident on ONE card — the offload moves the table, not the experts — so it cannot run on a 48 GB Ada card at all). ⚠ **PERSIST the cap** (systemd unit + persistence mode, ordered before Docker): a hand-set limit stops holding at the next reboot, which is likely to be the very power event it existed to prevent. → `docs/runbooks/fv-site-dark-20260913.md`