Written while the site is down so recovery does not have to be reconstructed later.
Records what was measured rather than what is suspected: every FV address including
the BMC is unreachable while all three other sites answer, the campaign's last log
line was off_A rep 2 at 06:56:04Z, and the site was dark by 06:58:40Z.
Names three candidate causes with the evidence that would distinguish them, because
the instrument that could have settled it -- the per-card power log -- died with the
box. The two-card-load hypothesis fits the timing and the two prior Anaheim breaker
trips on this same chassis, but it is circumstantial and is recorded as such.
Carries the recovery hazard that matters: every seat on the box is
restart:unless-stopped, so resetting power alone brings ten vLLM containers up
loading at once -- the largest transient the box can produce, into a circuit that may
have just tripped. Staged sequence given, gen first and flash-next last.
Also records the OOB gap the outage exposes: OPNsense-as-subnet-router protects
against box-down/gateway-up, and not at all against the site-wide loss that actually
happened, because the BMC's only path out is through that same gateway.